Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/29/2010 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) BOND GUTTER 2) NEED PROTECTIVE BUSHINGS 3) NEED 22 KAIL BREAKERS IN PANEL 4) MARK "SERVICE DISCONNECTS" |
|
| 12/07/2009 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) UFER TO BE MINIMUM 2" FROM BOTTOM OF FOOTING 2) NEED SEPERATE PERMIT FOR TEMP SERVICE OR GET TEMP SERVICE ADDED TO PERMIT |