Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DUCT NOT SECURED TO UNIT 2. MISSING P-TRAP 3. CONDENSATE TO BE SUPPORTED ON BLKS 4. HOLES K.O's IN DISCONNECT 5. LOOSE CONNECTION FLEX TO DISCONNECT, ROOF JACK TO FLEX 6. WHIP NOT SECURED 6" FROM BOX 7. PAINT CONDENSATE WITH LATEX PAINT |