Permit: T08CM00583

Parcel: 136176060


Addresses:

8319 E STELLA RD

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/11/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/10/2008 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
2. CALL IN RECONNECT INSPECTION & FINISH ALL ITEMS FROM RECONNECT INSPECTION
02/29/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN SAFE WORKING SPACE IN FRONT OF PANEL 110.26
2. USE APPROVED METHODS FOR CONNECTING LB'S
3. DERATE CONDUCTORS PER 310.15
4. WHITE CANNOT BE USED AS AN UNGROUNDED CONDUCTOR IN RACEWAYS
5. CABLES TO SECURE TO BACK OF BOX 312.5(C)
6. VERIFY CONDUCTOR FILL FOR GUTTER
7. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS
8. BOND RISER
9. VERIFY GROUND RODS LOCATIONS
10. DO NOT RING ALUMINUM CONDUCTORS PER MANUFACTURE
11. ID TAPE TO ENCIRCLE CONDUCTOR
12. A PERMANENT METAL ADDRESS LABEL IS NEEDED
13. IDENTIFY GROUNDED CONDUCTOR IN UTILITY SECTION
14. LABEL CIRCUIT BREAKER PER 408.4
15. USE APPROVED SIZED WIRE NUTS
16. CALL FOR RECONNECT 02070 ALSO AND NEED INTERIOR ACCESS
17. VERIFY GAS BOND