Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/10/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 2. CALL IN RECONNECT INSPECTION & FINISH ALL ITEMS FROM RECONNECT INSPECTION |
|
| 02/29/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN SAFE WORKING SPACE IN FRONT OF PANEL 110.26 2. USE APPROVED METHODS FOR CONNECTING LB'S 3. DERATE CONDUCTORS PER 310.15 4. WHITE CANNOT BE USED AS AN UNGROUNDED CONDUCTOR IN RACEWAYS 5. CABLES TO SECURE TO BACK OF BOX 312.5(C) 6. VERIFY CONDUCTOR FILL FOR GUTTER 7. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS 8. BOND RISER 9. VERIFY GROUND RODS LOCATIONS 10. DO NOT RING ALUMINUM CONDUCTORS PER MANUFACTURE 11. ID TAPE TO ENCIRCLE CONDUCTOR 12. A PERMANENT METAL ADDRESS LABEL IS NEEDED 13. IDENTIFY GROUNDED CONDUCTOR IN UTILITY SECTION 14. LABEL CIRCUIT BREAKER PER 408.4 15. USE APPROVED SIZED WIRE NUTS 16. CALL FOR RECONNECT 02070 ALSO AND NEED INTERIOR ACCESS 17. VERIFY GAS BOND |