Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM00580
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED CLEAN BACTERIA REPORT FOR POTABLE WATER |
|
| 05/13/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - BOTH SINKS REQUIRE CLEANOUTS - SUPPORT THE MIXING VALVES UNDER THE LAVATORIES - THE SINK IN THE BATHROOM IS CONSIDERED A HAND WASHING SINK AND REQUIRES A MIXING VALVE - CONTRACTOR TO PAY REINSPECTION FEE - REQUIRE NOTICE IN ELECTRIC SERVICE PANEL - "THIS BLDG HAS NON-METALLIC INTERIOR WATER PIPING" |
|
| 05/01/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE COPY OF BACKFLOW CERTIFICATION SEAL EXTERIOR WALL PENETRATION 2. PROVIDE COPY OF CLEAN BACTERIA REPORT 3. HOT & COLD PIPING FOR THE FIRST EIGHT FEET TO AND FROM WATER HEATER TO BE INSULATED PER 2006 IECC ALSO, INSTALL HEAT TRAPS OR HEAT TRAP FITTINGS AT WATER HEATER 4. PROVIDE HAMMER ARRESTORS AT WASHER BOX PER 609.10 2006 UPC 5. PROVIDE MIXING VALVE AT PUBLIC USE LAVATORY CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE |