Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00580
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2008 | ELECTRIC - FINAL | Approved | ||
| 05/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED. NO ACCESS. NO PLANS AVAILABLE. |
|
| 05/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED METAL LABELS FOR "SERVICE DISCONNECT" AND ADDRESS 2. PLANS NOT APPROVED, SHOW INCORRECT INFORMATION FOR SERVICE AND SUB-PANEL 3. NEED IRREVERSIBLE CRIMP OR WELD FOR G.E.C 4. ISOLATED GROUND TO RUN BACK TO SOURCE? |
|
| 05/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SINGLE LINE DIAGRAM NOT CORRECT/DOES NOT REFLECT ACTUAL EXISTING SERVICE 2. GROUNDING & BONDING CONDUCTORS ARE MISSING/STOLEN FROM SERVICE 3. IDENTIFY "SERVICE DISCONNECT" AS SUCH AND INSTALL SPACE NUMBER 4. PANEL DIRECTORY TO BE CORRECT, LEGIBLE, NO MISSPELLED OR ABBREVIATED WORDS, SPECIFY WHAT CKT IS GOING TO, ELECTRICAL TAPE NOT ACCEPTABLE |