Permit: T08CM00563

Parcel: 141351030

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T08CM00563

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/14/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) 2 X 12'S NEEDED AT STAIRWAY
2) HOLDOWNS NEED ANCHORS
3) HOLDOWNS BY FRONT DOOR ARE EPOXY SETS
4) 2 ANCHORS WEST OF OVERHEAD DOOR
04/11/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OVER SPALLED MAS STRAPS WEST OVERHEAD DOOR OPENING
2) NAIL PROTECT PIPES AT SILL PLATES
3) STRAP BEAM PER 602 DETAIL BOTH ENDS GARAGE
4) PLAN CALLS FOR 2 X 12'S AT STAIRWAY LANDING
5) HOLDOWNS NEED ANCHORS
6) WRONG HEADER IN WINDOW BY PATIO DOOR
7) STRAP BEAM IN KITCHEN PER 602 DETAIL
04/10/2008 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SUPER