Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/10/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/09/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/30/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR CEILING 1. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330.30 2. MC NOT TO LAY ON GRID - NEC 300 3. HAVE OVERFILLED J-BOXES -- NEC 314.16 4. NEUTRALS #6 & SMALLER TO BE WHITE ENTIRE LENGTH NOT TAPE - NEC 200.6 5. SEAL UNUSED OPENINGS - NEC 110.12A |
|
| 05/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK HARD LID RESTROOM |