Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FANS TOO LOW 2. LABEL CIRCUITS PER 408.4 3. USE APPROVED LISTED BRACE KIT FOR RISER NEAR TOP OF RISER 4. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS 250.64 5. FINISH #8 & 11, 13 OF PREVIOUS INSPECTION 6. INSTALL REJECTION PINS |
|
| 07/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECALL INSPECTION WHEN CONTR. ON SITE |
|
| 06/30/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR SERVICE 1. SERVICE DROP TO HAVE 18" CLEARANCE TO GROUND NEC 230.24B 2. INSTALL ADDRESS ON SERVICE 3. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B 4. DRIVE GROUND RODS FLUSH - NEC 250.53G 5. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO NEUTRAL - NEC 250.24A 6. RE-GROUND PHONE TO NEW SERVICE - NEC 800 7. INSTALL SERVICE FUSES - NEC 310 8. BOND RACEWAY BETWEEN METER AND DISCONNECT NEC 250.92 9. TIGHTEN MAIN BONDING SCREW IN DISCONNECT NEC 110.13 10. BOND METAL PIPES TO SERVICE DISCONNECT - NEC 250.104 11. RUN GROUNDING ELECTRODE CONDUCTOR TO PROTECT IT FROM BEING STOLEN 12. PROVIDE 36" FRONT WORKING PLATFORM FOR SERVICE NEC 110.26 13. NEED A LISTED MAST BRACE - NOT EMT NEC 230.28 |
|
| 05/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER |
|
| 05/14/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* RECALL WHEN READY |