Permit: T08CM00556

Parcel: 106120120


Addresses:

1475 W PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FANS TOO LOW
2. LABEL CIRCUITS PER 408.4
3. USE APPROVED LISTED BRACE KIT FOR RISER NEAR
TOP OF RISER
4. GROUNDING ELECTRODE CONDUCTOR TO BE
CONTINUOUS 250.64
5. FINISH #8 & 11, 13 OF PREVIOUS INSPECTION
6. INSTALL REJECTION PINS
07/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECALL INSPECTION WHEN CONTR. ON SITE
06/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
INSPECTION FOR SERVICE
1. SERVICE DROP TO HAVE 18" CLEARANCE TO GROUND
NEC 230.24B
2. INSTALL ADDRESS ON SERVICE
3. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B
4. DRIVE GROUND RODS FLUSH - NEC 250.53G
5. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO NEUTRAL - NEC 250.24A
6. RE-GROUND PHONE TO NEW SERVICE - NEC 800
7. INSTALL SERVICE FUSES - NEC 310
8. BOND RACEWAY BETWEEN METER AND DISCONNECT
NEC 250.92
9. TIGHTEN MAIN BONDING SCREW IN DISCONNECT
NEC 110.13
10. BOND METAL PIPES TO SERVICE DISCONNECT - NEC 250.104
11. RUN GROUNDING ELECTRODE CONDUCTOR TO PROTECT IT FROM BEING STOLEN
12. PROVIDE 36" FRONT WORKING PLATFORM FOR SERVICE
NEC 110.26
13. NEED A LISTED MAST BRACE - NOT EMT
NEC 230.28
05/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER
05/14/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
RECALL WHEN READY