Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/31/2008 | ELECTRIC - FINAL | Approved | ||
| 03/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EXISTING NM CABLE WIRING PER THE 1971 NEC DID NOT MEET THE REQUIREMENTS OF 517-51(b)(3) A SEPARATE INSULATED, CONTINUOUS, STRANDED, COPPER GROUNDING CONDUCTOR, NOT SMALLER THAN NO. 12 AWG, SHALL BE INSTALLED WITH THE CIRCUIT CONDUCTOR IN THE APPROVED WIRING SYSTEM WHICH CONNECTS EACH PATIENT RECEPTACLE... *UNDER 517.50 SEE NOTE FOR HAZARDS ASSOCIATED WITH PATIENT CARE AREAS 2. FINISH #1 & #2 PREVIOUS INSPECTIONS |