Permit: T08CM00542

Parcel: 13317062A

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00542

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/31/2008 ELECTRIC - FINAL Approved
03/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EXISTING NM CABLE WIRING PER THE 1971 NEC DID NOT MEET THE REQUIREMENTS OF 517-51(b)(3) A SEPARATE INSULATED, CONTINUOUS, STRANDED, COPPER GROUNDING CONDUCTOR, NOT SMALLER THAN NO. 12 AWG, SHALL BE INSTALLED WITH THE CIRCUIT CONDUCTOR IN THE APPROVED WIRING SYSTEM WHICH CONNECTS EACH PATIENT RECEPTACLE...

*UNDER 517.50 SEE NOTE FOR HAZARDS ASSOCIATED WITH PATIENT CARE AREAS

2. FINISH #1 & #2 PREVIOUS INSPECTIONS