Permit: T08CM00532

Parcel: 141093330


Addresses:

6517 E STADIUM PW

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RANGE RATED AT 12, 5000 WATTS=APPROX 52.8 AMPS RANG CIRCUIT IS A #6 AL.=AT 75 DEGREE=50 AMPS AT 60 DEGREE=40 AMPS
2) BLANK OF RECEPT UNDER KIT COUNTER OVER HANG
3) NOTE: MAKE SURE YOU HAVE ALL CERTS
06/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/07/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled