Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RANGE RATED AT 12, 5000 WATTS=APPROX 52.8 AMPS RANG CIRCUIT IS A #6 AL.=AT 75 DEGREE=50 AMPS AT 60 DEGREE=40 AMPS 2) BLANK OF RECEPT UNDER KIT COUNTER OVER HANG 3) NOTE: MAKE SURE YOU HAVE ALL CERTS |
|
| 06/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/07/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |