Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T08CM00532
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
04/07/2008 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NOTE: NEED PLAN CHANGE FOR LAG CONNECTION POST TO BEAM PORCH |
|
04/03/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) HPAHD 42 HOLDOWNS REQUIRED PER PLAN K.C. TYPE SA2545 USED = EQUAL ? 2) NEED BC 42 POST TO BEAM CONNECTION REAR PORCH 3) <3> #3 SHEAR WALL GARAGE BLK ? NEEDED AT TOP OF WALL 4) MISSED NAILING ON ROOF MARKED IN BLACK 5) AT GARAGE SHEAR TRANSFER HOUSE TO GARAGE WALL 6" ON CENTER NAILING MIN. TWO TRUSSES |