Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM00522

Parcel: 13104405A


Addresses:

4925 E 29TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00522

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
DUCT SMOKE TEST OK
07/11/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALL AND FUSE ACCORDINGLY.

PERMANENTLY I.D AC UNITS WITH ADDRESS & UNIT NUMBER
SEAL ALL SEAMS & SPOT WELDS ON EXPOSED DUCT
PROVIDE MIN. 2" R-8 DUCT LINER IN EXPOSED DUCT ON ROOF
PROVIDE AIR FILTERS
07/09/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*