Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00522
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPLACE PAINTED OVER DEVICES 2. EM LIGHTING TO BE TIED IN WITH LIGHTING CIRCUIT FOR THE AREA 3. INSTALL GE BREAKERS IN GE PANELS 4. ROOFTOP UNITS OVERFUSED. MARK NAMEPLATE 5. NEED ROOFTOP GFI SERVICE RECEPTACLE WITHIN 25' OF AC UNITS 6. INSTALL BONDING SCREW IN A/C DISCONNECTS |
|
07/09/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |