Permit: T08CM00522

Parcel: 13104405A


Addresses:

4925 E 29TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00522

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPLACE PAINTED OVER DEVICES
2. EM LIGHTING TO BE TIED IN WITH LIGHTING CIRCUIT FOR THE AREA
3. INSTALL GE BREAKERS IN GE PANELS
4. ROOFTOP UNITS OVERFUSED. MARK NAMEPLATE
5. NEED ROOFTOP GFI SERVICE RECEPTACLE WITHIN 25' OF
AC UNITS
6. INSTALL BONDING SCREW IN A/C DISCONNECTS
07/09/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled