Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00515
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2008 | ELECTRIC - FINAL | Approved | ||
03/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDING ISSUE TAKEN CARE 2. EM LIGHTING NOT WORKING |
|
03/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SUPPORT 3/0 ABOVE CEILING IN A WORKMANSHIP LIKE MANNER. WHERE IS GAS PIPE BOND? OPEN UP SERVICE EQUIP. FOR INSPECTION. |
|
02/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUNDING AND BONDING JUMPERS TO WATER PIPING, GAS PIPING, ETC. HAVE BEEN CUT AND REMOVED. NOT SURE IF GROUNDING ELECTRODE CONDUCTOR INVESTIGATE GROUNDING & BLDG SERVICE 2) ABOVE ITEMS TO BE CORRECTED BEFORE FINAL WILL BE APPROVED 3) RECALL FOR FINAL WHEN READY. HAVE SOMEONE CHECK EM LIGHTING |