Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00510
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO MORE THAN 360 DEG. IN A CONDUIT RUN 2. SUPPORT CONDUITS WITHIN 3' OF BOXES 3. SUPPORT BOXES 4. GROUND TOP & BOTTOM RAILS AND AROUND SPLICES 5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING 6. MAINTAIN WORKING CLEARANCES 110.26 7. ONLY ONE CONDUCTOR PER TERMINAL LUG 8. INSTALL GROUNDING ELECTRODES PER 250.52 9. ILLUMINATION IS NEEDED 110.26(D) 10. FUSES TO BE DC RATED 11. FINISH LABELING PER 690.17 12. LOCKNUT INSTALLED BACKWARDS 13. SEPARATE NEUTRALS & GROUNDS AT PANEL 14. ONLY ONE NEUTRAL TERMINATION TO A LUG 15. A GROUND BAR IS NEEDED AT PANEL 16. GROUNDS TO REMAIN #8 AS PER PLANS 17. BOND GROUNDING ELECTRODES AS PER PLANS 18. PLEASE VERIFY PERMIT FOR DOORWAY BLOCKING DISCONNECTS |