Permit: T08CM00510

Parcel: 121136430


Addresses:

5350 E ERICKSON DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00510

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NO MORE THAN 360 DEG. IN A CONDUIT RUN
2. SUPPORT CONDUITS WITHIN 3' OF BOXES
3. SUPPORT BOXES
4. GROUND TOP & BOTTOM RAILS AND AROUND SPLICES
5. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING
6. MAINTAIN WORKING CLEARANCES 110.26
7. ONLY ONE CONDUCTOR PER TERMINAL LUG
8. INSTALL GROUNDING ELECTRODES PER 250.52
9. ILLUMINATION IS NEEDED 110.26(D)
10. FUSES TO BE DC RATED
11. FINISH LABELING PER 690.17
12. LOCKNUT INSTALLED BACKWARDS
13. SEPARATE NEUTRALS & GROUNDS AT PANEL
14. ONLY ONE NEUTRAL TERMINATION TO A LUG
15. A GROUND BAR IS NEEDED AT PANEL
16. GROUNDS TO REMAIN #8 AS PER PLANS
17. BOND GROUNDING ELECTRODES AS PER PLANS
18. PLEASE VERIFY PERMIT FOR DOORWAY BLOCKING DISCONNECTS