Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. PROVIDE ACCESS DOORS AT FIRE DAMPERS 2. PROVIDE PROPER INSTALLATION OF FLANGE RINGS AT FIRE DAMPERS 3. ABOVE TO BE COMPLETED PRIOR TO FINAL 4. STENCIL ACCESS DOORS |
|
| 07/22/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO PROGRESS NEXT FAILED INSPECTION WILL REQUIRE A REFEE |
|
| 07/21/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DUCT TAPE OFFS NOT PER PLANS, DETAILS AND SPECS 2. SEAL ALL DUCT 3. SPIRAL PIPING NOT HUNG PER DETAIL 4. EXHAUST FLEX NOT MECHANICALLY FASTENED 5. PROVIDE CONDENSATE PIPING REFER TO DETAILS 5/M1.1, 7/M1.1, 8/M1.1, 6/M1.1 REFER TO SPECS 2.01, 2.02, 2.03, 3.03, 3.04 |