Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2008 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
| 09/11/2008 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
| 09/10/2008 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* BOND FOR TEMP POWER? |
|
| 08/21/2008 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* OK TO CLEAR #141 SUBJECT TO POSTING OF BOND TMPP COMM OK 3/0 TO 2 GROUND RODS |
|
| 08/20/2008 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED NO ACCESS |
|
| 08/19/2008 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE TO CONNECT TO GROUNDED TERMINAL 2. INSTALL GROUNDING ELECTRODE TAPS 3. BOND RACEWAYS PER 250.92 4. SUPPORT CONDUITS 5. CLOSE UNUSED CONDUIT OPENINGS |
|
| 08/12/2008 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* |