Permit: T08CM00501

Parcel: 10925013B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/26/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/21/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/14/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE ROMEX FROM DROP CEILING AREA
2. HAVE OPEN JUNCTION BOXES
3. HAVE MC CABLE NOT TERMINATED
4. INSTALLATION NOT PER PLAN. INSTALL PER PLAN OR REVISE PLAN
5. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE CEILING INSTALL PER PLAN AND NEC. RECALL WHEN READY.