Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED DETAILED PANEL SCHEDULE 2. EXPOSE GROUND RODS OR INSTALL IF NOT INSTALLED 3. BOND GAS & WATER PIPING 4. INSTALL LISTED MAST BRACING 5. CANNOT USE SELF-TAPPING SHEETMETAL SCREW FOR CONNECTION OF GROUNDS 12X12 J.B 6. BLANK OPEN BREAKER POSITION IN DEAD FRONT 7. STRAP RACEWAYS WITHIN 3' OF CONNECTION TO PANEL BOXES 8. INSTALL PROPER CONNECTOR FROM PANEL TO SINGLE GANG BELL BOX BOTTOM OF PANEL 9. CANNOT SEE INTO METER SECTION PANEL ENERGIZED PRIOR TO APPROVALS |