Permit: T08CM00489

Parcel: 116122650


Addresses:

1320 W SONORA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/27/2014 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/05/2014 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/05/2014 ELECTRIC - FINAL Denied PROVIDE UFER, GAS/WATER BOND. PINCHED WIRE AT STOVE. PROVIDE COMBUSTION AIR FOR W/H
05/28/2014 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/21/2014 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/21/2014 ELECTRIC - FINAL Not ready for Inspection DEADFRONT FOR PANEL, #14 WIRE ON 15 AMP MAX BREAKER. VERIFY MULTI-WIRE CIRCUITS ON SEPARATE PHASE