Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/05/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/05/2014 | ELECTRIC - FINAL | Denied | PROVIDE UFER, GAS/WATER BOND. PINCHED WIRE AT STOVE. PROVIDE COMBUSTION AIR FOR W/H | |
| 05/28/2014 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/21/2014 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/21/2014 | ELECTRIC - FINAL | Not ready for Inspection | DEADFRONT FOR PANEL, #14 WIRE ON 15 AMP MAX BREAKER. VERIFY MULTI-WIRE CIRCUITS ON SEPARATE PHASE |