Permit: T08CM00484

Parcel: 13323164A


Addresses:

7150 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM00484

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/08/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FS AND FOAMS OK AT REFRIGERATOR CASE
08/07/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) ROUGH SOIL PIPING WITH TEST OK
2) RECALL INSPECTION PRIOR TO CONCRETE FOR FS, FCO INSTALLATIONS AND FOAM WRAPS
3) NOTE: DRAINAGE FITTINGS INSTALL IN THE DIRECTION OF FLOW ARE REQUIRED BY ? FOR TESTING
08/06/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLASTIC PIPING MAY NOT BE TESTED WITH AIR UPC 712
2) PVC FEMALE FITTINGS MAY NOT BE LOCATED IN NON ACCESSIBLE LOCATIONS IS #9, 316.1.5
3) EXTEND RISERS AT CO LOCATIONS TO 8'
07/21/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
AFTER HRS. INSP. CHK#0635920971

PVC DWV UNDERGROUND WITH PIPE WRAPS, TRAP PRIMER AND FLOOR DRAIN TO 2" AFF TEST OK (PHARMACY ONLY)
07/18/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PHARMACY

ABS PLASTIC PIPING MAY NOT BE TESTED W/AIR
PLAN SPECS PVC OR C1 NOT ABS
WILL ACCEPT A LETTER FROM YOUR ENGINEER
APPROVED PLANS SHALL BE ON SITE FOR INSP.
NOT INSTALLED PER PLAN
FOLLOW YOUR PIPING RISER DIAGRAM
CONVENTIONAL VENTING
RISER FOR LAV
PROVIDE MIN. TRAP ARM DISTANCE AND END OF RUN CO
OK TO WRAP W/FOAM AND INSTALL FD IF YOU'D LIKE