Permit: T08CM00484

Parcel: 13323164A


Addresses:

7150 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T08CM00484

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2008 FRAMING Approved IVRS - Inspection :*
PLYWOOD SHEATING ON INTERIOR PHARMACY WALLS
OK TO COVER
07/21/2008 FRAMING Partial Approval IVRS - Inspection :*
PHARMACY REF. PP. PH1

1. CAUTION! YOUR PLANS CALL FOR WATER CLOSET TO BE 18" FROM SIDE WALL @ FINISH (1'6 1/2" AT ROUGH) YOU HAVE ROUGHED IN AT 16 1/2". YOU WILL NEED TO BE 16"-18" TO CENTER @ FINAL

ALSO, FINISH INSTALLING BLOCKING
07/10/2008 FRAMING Partial Approval IVRS - Inspection :*
TEMPORARY PHARMACY AS PER OPTION "C" PAGE TCI