Permit: T08CM00479

Parcel: 13342634P


Addresses:

2096 N KOLB RD #104

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT VDV CABLING AND USE APPROVED BOXES
2. A GROUNDING EQUIPMENT CONDUCTOR IS NEEDED FOR WOMENS INSTA-HOT
3. OFFICE FURNITURE TO BE AS PER 605.7
4. TIGHTEN LOOSE FITTINGS
5. MAKE UP TO BE ACCESSIBLE
6. VDV CABLING NOT AS DISCUSSED - SUPPORT AS PER 300.11 ALSO, NOT TIE WIRE USE A #12 CEILING TYPE WIRE