Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE PAINT @ LUG CONNECTION FOR GROUNDING IN DISCONNECT 2. PROPERLY TIGHTEN GROUND CONNECTIONS IN DISCONNECT 3. CANNOT USE SHEETMETAL SCREWS FOR GROUND BAR CONNECTION IN PANEL 4. BACK FED BREAKERS TO BE MECHANICALLY SECURED TO PANEL 5. BONDING JUMPER FROM NEUTRAL TO GROUND NOT SIZED PROPERLY TO BE #4 6. INSTALL PROPER SIZE BREAKER FOR XFMR & TERMINATE WIRES. PROPERLY MARK DISCONNECT FOR XFMR |