Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2008 | ELECTRIC - INTERMEDIATE | Approved | ||
| 03/13/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. BOX OVERFILLED 2. SUPPORT MC CABLE WITHIN 12" OF BOXES 3. FILL UNUSED OPENINGS IN PANEL & BOXES 4. REMOVE BOND SCREW FROM NEUTRAL 5. TIGHTEN LOOSE FITTINGS 6. PLANS SAY REPAIR - THIS IS A COMPLETE REWIRE CHECK WITH PLAN CHECK FOR REQUIREMENTS TO REVISE PLANS CIRCUITS, LOADS, ETC. |