Permit: T08CM00457

Parcel: 110055340

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00457

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
SEE BUILDING INSPECTOR FOR TEMP C OF O
06/18/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BALANCE REPORT INDICATES NO VOLUME DAMPERS IN SYSTEM WHICH IS THE REASON FOR NON-COMPLIANCE WITH THE PLANS AND SPECS. I PERSONALLY CLIMBED INTO THE ATTIC AND FOUND THE BRANCH TAPS TO HAVE VOLUME DAMPERS. THIS SYSTEM WILL BE BALANCED PER PLANS AND REPORTS FROM THIS BALANCE TECHNICIAN WILL NOT BE ACCEPTED ON THIS PROJECT.