Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* LINER INSTALLED WITHOUT INSPECTION WATER TEST TO FLOOD LEVEL OK |
|
| 05/16/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE WATER TEST TO FLOOD LEVEL ABV CEILING OK EXCEPT STEAM UNIT NOT YET INSTALLED |
|
| 04/11/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED TO SEE SHOWER SET FLANGE OK OK TO COVER WALLS OK TO COVER OVERHEAD |
|
| 04/10/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ALL FIXTURES REQUIRE SHUT OFF'S 2. NEED TO SEE THE SHOWER INSTALLED AND MOP SINK 3. SECURE RISERS MID-STORY ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS ABS SHIM NOT APPROVED SUPPORT |
|
| 04/07/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - FIP THREADED FITTINGS SHALL NOT BE CONCEALED SEE UPC IS #5 - INSTALL SOLVENT WELD TEST TEES - SUPPORT HORIZONTAL ABS IN WALLS TO PROTECT FROM SHARP METAL - SUPPORT ABV CEILING VENTS PER T 3-2 AND PLAN SPECS - SECURE RISERS MID-STORY - SECURE DROP EAR ELL AT SHWR HEAD - INSULATE PER SPEC OR PROVIDE ARCHITECT APPROVAL AND SEAL ALL JOINTS |