Permit: T08CM00457

Parcel: 110055340

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/25/2008 ELECTRIC - FINAL Approved
06/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH GROUNDING ELECTRODE CONDUCTOR
06/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ITEMS 1, 2, 3, 5, 8 & PLAN REVISIONS
06/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUNDING ELECTRODE CONDUCTOR MISSING AT SERVICE
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING - 314.20
3. CLEAN EXCESS PAINT & FOREIGN MATERIAL FROM DEVICE TERMINALS 110.12
4. GFCI'S NOT WORKING
5. SECURE DEVICE TO BOX6. FINISH VDV CABLING
7. WATER HEATER: TIGHTEN LOOSE FITTINGS, INSTALL FUSES, CONDUCTOR NOT ALLOWED TO BE WHITE AND TAPE A COLOR IN A RACEWAY REMOVE SERVICE DISCONNECT LABEL AND IDENTIFY
8. NO PANEL DIRECTORY - LABEL AS PER 404.8
9. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL
10. EMERGENCY LIGHTS TO BE ON AREA SERVED (700.12)
11. STEAM GENERATOR: CORRECTLY LABEL DISCONNECT, PLANS CALL FOR A 30 AMP CIRCUIT WE HAVE A 40 AMP CIRCUIT
06/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REVISED PLAN NOT SHOWING ALL ADDED OUTLETS