Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2008 | ELECTRIC - FINAL | Approved | ||
| 06/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH GROUNDING ELECTRODE CONDUCTOR |
|
| 06/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ITEMS 1, 2, 3, 5, 8 & PLAN REVISIONS |
|
| 06/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE CONDUCTOR MISSING AT SERVICE 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING - 314.20 3. CLEAN EXCESS PAINT & FOREIGN MATERIAL FROM DEVICE TERMINALS 110.12 4. GFCI'S NOT WORKING 5. SECURE DEVICE TO BOX6. FINISH VDV CABLING 7. WATER HEATER: TIGHTEN LOOSE FITTINGS, INSTALL FUSES, CONDUCTOR NOT ALLOWED TO BE WHITE AND TAPE A COLOR IN A RACEWAY REMOVE SERVICE DISCONNECT LABEL AND IDENTIFY 8. NO PANEL DIRECTORY - LABEL AS PER 404.8 9. CLEAN EXCESS DIRT FROM BOTTOM OF PANEL 10. EMERGENCY LIGHTS TO BE ON AREA SERVED (700.12) 11. STEAM GENERATOR: CORRECTLY LABEL DISCONNECT, PLANS CALL FOR A 30 AMP CIRCUIT WE HAVE A 40 AMP CIRCUIT |
|
| 06/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REVISED PLAN NOT SHOWING ALL ADDED OUTLETS |