Permit: T08CM00428

Parcel: 137277490


Addresses:

1651 W HOUCHIN WY

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/26/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PREVIOUS
02/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL KNOCKOUTS BOTTOM MAIN SERVICE PANEL PER PREVIOUS NOTE 6
02/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SEE NOTE #4 LAST INSP.
- RECALL INSPECTION
- NO ANSWER AT DOOR
02/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL DISCONNECT FOR WATER HEATER - NEC 422.31
2. MAKE CONNECTIONS TO WATER IN JUNCTION @ WATER HEATER PROVIDED FOR BY MANUFACTURE
3. PROPERLY GROUND WATER HEATER
4. CANNOT DOUBLE TAP BREAKERS FOR CLOTHES DRYER INSTALL SEPARATE BREAKER FOR WATER HEATER
5. INSTALL SCHEDULE 80 PVC & GLUE ALL CONNECTIONS
AND USE LISTED FITTINGS FOR PVC. CANNOT USE
SCHEDULE 40 PVC WHEN RUN EXPOSED.
6. SEAL OPEN KNOCK OUT BOTTOM OF PANEL
7. PROPERLY STRAP PVC