Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/26/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH PREVIOUS |
|
| 02/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL KNOCKOUTS BOTTOM MAIN SERVICE PANEL PER PREVIOUS NOTE 6 |
|
| 02/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SEE NOTE #4 LAST INSP. - RECALL INSPECTION - NO ANSWER AT DOOR |
|
| 02/13/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL DISCONNECT FOR WATER HEATER - NEC 422.31 2. MAKE CONNECTIONS TO WATER IN JUNCTION @ WATER HEATER PROVIDED FOR BY MANUFACTURE 3. PROPERLY GROUND WATER HEATER 4. CANNOT DOUBLE TAP BREAKERS FOR CLOTHES DRYER INSTALL SEPARATE BREAKER FOR WATER HEATER 5. INSTALL SCHEDULE 80 PVC & GLUE ALL CONNECTIONS AND USE LISTED FITTINGS FOR PVC. CANNOT USE SCHEDULE 40 PVC WHEN RUN EXPOSED. 6. SEAL OPEN KNOCK OUT BOTTOM OF PANEL 7. PROPERLY STRAP PVC |