Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00424
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO LADDER ON SITE TO CHECK HEAT PUMP ON ROOF PAY REFEE BEFORE NEXT INSPECTION |
|
05/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ELECTRICIAN WORKING ON CORRECTIONS FROM PREVIOUS INSPECTION. RECALL WHEN READY. |
|
05/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLES WITH OPEN GROUNDS 2. RECEPTACLE NO POWER 3. HEAT PUMP OVER FUSED 4. TIGHTEN ALL FITTINGS ON ROOF 5. STRAP SEAL TIGHT WITHIN 12" OF CONNECTION TO DISCONNECT 6. INSTALL BONDING BUSHING ON SEAL TIGHT CONNECTOR THROUGH CONCENTRIC KNOCK OUTS HP DISCONNECT. |