Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INSTALL SEAL OFF AS DISCUSSED RECALL WHEN COMPLETE |
|
| 06/26/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WORK BY CONTRACTOR 100% COMPLETE & OK 2. EQUIPMENT HOOK UP TO BE DONE BY TENANT. ALL THIS WORK NEEDS TO BE INSPECTED 3. CHECK WITH BUILDING INSPECTOR FOR TEMP C OF O 4. RECEPTACLES MOUNTED IN INDUSTRIAL COVERS TO BE MOUNTED WITH ALL HARDWARE PROVIDED |
|
| 06/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLAN CALLS FOR SWITCHGEAR TO BE RATED FOR 100 KAIC LABELING OF GEAR STATES RATING TO BE 65 KAIC 2. SECURE GEAR TO CONCRETE PAD 3. OK WIRING TO XFMRS 300KVA |