Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 02/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 2. PROPERLY WIRE TRACK LIGHT ABOVE KITCHEN SINK CANNOT HAVE OPEN WIRING 3. SAFE OFF WIRES @ OPEN JUNCTION IN BEDROOM & BLANK OPEN BOX 4. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS 5. AC SMOKE DETECTOR IN HALLWAY TO HAVE BATTERY BACK UP POWER 6. INSTALL MISSING SWITCH PLATE & RECEPTACLE PLATE 7. CLOSET LIGHT MSTR. BDRM. TO BE 100% ENCLOSED 8. INSTALL BREAKERS LISTED FOR USE IN BRYANT PANEL 9. SEAL OPEN BREAKER POSITIONS @ PANEL 10. OUTDOOR RECEPTACLES TO BE GFI PROTECTED 11. OUTDOOR RECEPTACLES TO HAVE WEATHERPROOF COVER 12. VERIFY PERMIT FOR NEW AC UNIT. PROVIDE COPY @ NEXT INSPECTION |