Permit: T08CM00406

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00406

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
PAID CK#2729
4/15/08
$150.00
04/15/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
INTERLOCK EX. FANS TO AC
04/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMERGENCY LIGHTING TO BE PER NEC 700.12F
2. HAVE ISOLATED GROUND RECEPTACLES BUT NO ISOLATED GROUND
3. HOW IS POS COUNTER FED? HAVE MC FROM DOUBLE DUPLEX BEHIND P.O.S COUNTER?
4. ALL LOW VOLTAGE WIRING TO BE SUPPORTED TO STRUCTURE - NOT TO OTHER EQUIPMENT
5. FIRE ALARM WIRING TO BE RED, FIRE NOT COMPLETE
6. PANEL DIRECTORY NOT CORRECT