Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00406
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PAID CK#2729 4/15/08 $150.00 |
|
04/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS INTERLOCK EX. FANS TO AC |
|
04/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHTING TO BE PER NEC 700.12F 2. HAVE ISOLATED GROUND RECEPTACLES BUT NO ISOLATED GROUND 3. HOW IS POS COUNTER FED? HAVE MC FROM DOUBLE DUPLEX BEHIND P.O.S COUNTER? 4. ALL LOW VOLTAGE WIRING TO BE SUPPORTED TO STRUCTURE - NOT TO OTHER EQUIPMENT 5. FIRE ALARM WIRING TO BE RED, FIRE NOT COMPLETE 6. PANEL DIRECTORY NOT CORRECT |