Permit: T08CM00402

Parcel: 13422114A


Addresses:

6880 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/30/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CLOSET FLANGES OK
06/27/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ALL AREAS DWV THRU ROOF OK
WATER HAMMER ARRESTORS OK
ABOVE CEILING IN 128 & 110 OK
RECALL FOR CLOSET FLANGES PRIOR TO STOOL
06/17/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
THIS INSPECTION FOR RESTROOMS #109, 111 AND
MOP SINK ROOM #110 ABOVE CEILING, PLEASE COMPLY WITH NOTES FROM 6/13/008 INSPECTION & PROVIDE WATER HAMMER ARRESTOR FOR FLUSH VALVES IN RESTROOMS AS REQUIRED BY 2006 UPC
06/13/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SUPPORT OVERHEAD HW PIPING PER PEX INSTALLATION
STANDARDS 32" AND USE PIPE SUPPORTS
06/06/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE ENGINEERS STAMPED SEALED LETTER FOR PEX AND ARMOR FLEX INSULATION
06/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DWV CORRECTIONS OK
2. MIDDLE PLUMBING WALL OK TO COVER
3. TRIM OUT ALL CLEANOUT/TEST TEES FOR FINAL
4. DFS EXCEPT AT 126 OK TO COVER
5. NEED TO INSPECT PIPE INSULATION

NOTE: HWR REQUIRES INSULATION PER CODE
ALSO, NEED TO INSPECT ABV CEILING PIPE SUPPORTS
PROVIDE LETTER FOR USE OF PEX
06/02/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DWV TEST THRU ROOF OK EXCEPT FOR P-9 IN HALL 126
2. CORRECT URINAL WASTE AND REMOVE UNACCESSIBLE PVC FEMALE THREADS
3. PEX OK PER SMU.
4. SECURE OR INSULATE FOR NOISE
5. TEST ON WATER OK
6. INSULATE HW AND HWR PER PLAN SPECS.
7. RECALL FOR INSPECTION
8. CLOSET FLANGES REQUIRE FIRM BASE AND FASTENERS
9. SEE UPC IS #9
05/22/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) THIS INSPECTION FOR GAS SYSTEM, BECAUSE OF CHANGES AND DEMO PROCESS, ALL PIPING WILL REQUIRE TO BE TESTED AND MEET 2006 UPC REQUIREMENTS