Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ALL ROOFTOP RACEWAYS TO BE PROPERLY SECURED AND SECURED TO ROOF. LOW VOLTAGE ALSO. 2. HP-1 OVERFUSED 3. HAVE SECTIONS OF METAL RACEWAYS ON ROOF NOT GROUNDED 4. ALL ROOFTOP BOXES TO BE WEATHERPROOF LOW VOLTAGE ALSO 5. MISSING GASKET ON COVER FOR GFI/GFI WILL NOT SEAT FIRMLY AGAINST BOX 6. SECURE DISCONNECTS TO ROOFTOP 7. TIGHTEN ALL FITTINGS ROOFTOP 8. HP-5 NAMEPLATE MARKING INDICATES CONDUCTOR SIZE AND FUSE SIZE TO SMALL |
|
| 07/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE ITEMS #3, 4, 5, 6, 7, 8, 9, 10, 12, 13, 14, 15 FROM INSPECTION ON 7/17/08 2. CHECK WITH BUILDING INSPECTOR FOR TEMP C OF O |
|
| 07/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING EM LIGHTS SOME EM LIGHTS NOT WORKING 2. BATHROOM RECEPT TO BE GFI 3. EXISTING RECEPT BROKEN NEED TO BE REPLACED 4. EXISTING ROOFTOP DISCONNECTS TO BE PROPERLY GROUNDED 5. EXISTING ROOFTOP RACEWAYS TO BE INSTALLED PER NEC 6. EXISTING ROOFTOP JUNCTION BOXES TO BE WEATHERPROOF 7. EXISTING ROOFTOP DISCONNECTS TO HAVE OPEN KNOCKOUTS SEALED 8. FINISH INSTALLING ROOFTOP GFI 9. INSTALL LOCKNUT ON NIPPLE IN GUTTER ROOFTOP 10. MARK NAMEPLATE FOR ROOFTOP UNITS 11. UNABLE TO CHECK PROPER FUSING IN EXISTING ROOF TOP UNITS CANNOT READ NAMEPLATE DATA 12. EXISTING ROOFTOP A/C DISCONNECT BLADES NOT MAKING CONTACT 13. ONE NEW ROOF TOP UNIT OVERFUSED 14. MARK "SERVICE DISCONNECTS" 15. PROPERLY SECURE A/C DISCONNECTS TO ROOF 16. NEED PANEL SCHEDULES |