Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY JAMES OF EDWARDS ELECTRIC |
|
| 11/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT CORD CONNECT INSTANT-HOTS USE DISCONNECTS AND WIRING METHOD OTHER THAN FLEXIBLE CORD 2. EM LIGHTING OUTDOORS NOT WORKING 3. PLAN CALLS FOR PANEL RATING TO BE 22KAIC |
|
| 11/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO GET HOUSE PANEL TURNED BACK ON FOR EGRESS LIGHTING 2) NEED TO HAVE POWER ON FOR FINAL |
|
| 10/29/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |