Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T08CM00386
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/29/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. BOND EXISTING SERVICE DISCONNECT NEUTRAL AND LABEL 2. PROVIDE PLAQUE TO INDICATE PLACMENT OF EXISTING SERVICE DISCONNECTS |
|
| 06/24/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SERVICE DISCONNECTS NOT GROUPED 230.71 |
|
| 06/09/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CALL FOR FOLLOW UP INSPECTION AFTER NEW SERVICE IS ENERGIZED |
|
| 06/04/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PARALLEL SETS OF FEEDERS MUST BE EQUAL FOR GROUNDS SIZES 2. DO NOT DAISY CHAIN BOND BUSHINGS UNLESS GROUND CONDUCTOR SIZED FOR TOTAL AMPERAGE OF ALL FEEDERS 3. REMOVE EQUIP. GROUNDS FROM NEUTRAL BARS IN SERVICE DISCONNECTS AND USE BOND SCREW ONLY FOR NEUTRAL BOND 4. HUBS FOR RISER CONDUITS MUST BE LISTED FOR BONDING AT SERVICE 5. GROUND RODS MUST BE 8' IN EARTH GROUNDING AND BONDING TO COMPLY WITH 250 NEC |