Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OK TO COVER ALL AREAS |
|
| 03/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ONLY EIGHT DRAINAGE FIXTURE UNITS PERMITTED ON A TWO INCH DRAIN 2. ONLY 24 DFU'S PERMITTED ON A 2% VENT 3. 2" VENT MAY ONLY BE RUN HORIZONTALLY FOR FORTY FEET |
|