Permit: T08CM00385

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM00385

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
03/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ONLY EIGHT DRAINAGE FIXTURE UNITS PERMITTED ON A TWO INCH DRAIN
2. ONLY 24 DFU'S PERMITTED ON A 2% VENT
3. 2" VENT MAY ONLY BE RUN HORIZONTALLY FOR FORTY FEET
03/06/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO STORE NUMBER POSTED
UNABLE TO LOCATE PLAN OR PERMIT
NO CONTACT NUMBER LEFT WITH MESSAGE
CONTINUED NOT READY WILL RESULT IN A REINSPECTION FEE