Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM00384
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 02/29/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE A SECONDARY DRAIN OVERFLOW SENSOR - PROVIDE A HOSE CLAMP ON PUMP & AT TRANSITION TO COPPER - REMOVE ALL TAPE FROM VENT CONNECTOR & PROVIDE MIN. 3 SCREWS IN EACH JOINT - DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP - FUSE STAT NOT REQUIRED - PROVIDE A ROMEX CONNECTOR ON FURNACE CORD - 3/8" X 48" GAS FLEX NOT ADEQUATE FOR 75,000 BTU & CANNOT EXCEED 3' IN LENGTH - EXTEND FURNACE VENT MIN. 2' ABOVE COMBUSTION AIR INTAKE |