Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE RED WIRE FOR EQUIPMENT GROUNDS NEED TO BE GREEN ALONG ENTIRE LENGTH 2. CONNECT EQUIPMENT GROUNDS TO LIGHT POLES 3. CANNOT USE BLUE WIRE FOR NEUTRAL NEED TO BE WHITE ALONG ENTIRE LENGTH 4. INSTALLATION NOT PER PLAN INSTALL FUSE HOLDER AND #10 WIRE PER DETAIL #5 ON A-1 5. SEAL OPEN KNOCK OUT JUNCTION BOX 6. CONNECT EQUIPMENT GROUND TO JUNCTION BOX |