Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00366
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY JOSH |
|
05/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK INTERIOR FIRST FLOOR MAIN BUILDING CLASSROOM 113 EMERGENCY LIGHTING TO BE VERIFIED FOR PROPER OPERATION AND COMPLIANCE WITH NEC 700.12F ALSO, ALL PANEL DIRECTORIES TO BE CORRECT AND SECURED TO PANELS. |
|
05/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY INSPECTION FOR PHASE ONE FIRST FLOOR 1. SPACE IS NOT TO BE OCCUPIED BY PEOPLE OR FURNITURE BEFORE APPROVAL 2. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN ALSO, NEED TO BE AIMED SO IT IS EFFECTIVE. 3. WORK NOT COMPLETE/IN PROGRESS 4. PANEL DIRECTORIES (ALL) TO BE CORRECT AND PERMANENT AND IDENTIFIED PER NEC 408.4 5. WHERE QUAD RECEPTACLES ADDED a. CONDUCTORS TO BE PROPERLY DERATED - NEC 310.15 b. J-BOX OVERFILLED - NEC 314.16 |