Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM00366
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/27/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES ROOMS 218-219-220 AFTER 2 FIXTURES IN ROOM 220 SECURED TO GRID IN FUTURE - DO NOT CALL BEFORE READY OR A FEE MAY BE CHARGED |
|
05/23/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT MC CABLE PER NEC 2. USE OF ENT NOT APPROVED PER PLAN? OBTAIN LETTER FROM ARCH. FOR USE 3. REMOVE ALL UNUSED CABLING. SUPPORT PER CODE. 4. HURRICANE CLIPS ON FIXTURE TO GRID NOT EFFECTIVE, INSTALL PROPERLY OR USE SCREWS, ELEC. CONTR. NOT ON SITE |
|
05/22/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
04/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES LOWER LEVEL PHASE 1 |
|
04/24/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL FIXTURES TO HAVE SUPPORT WIRES 2. REMOVE ABANDONED LOW VOLTAGE WIRING, NOT TO LAY ON GRID 3. INSTALL J-BOX COVERS 4. REMOVE/CLOSE UNUSED RACEWAYS 5. ALARM TRANSFORMER TO PLUG IN BELOW CEILING 6. NO MORE THAN 1 BOX EXTENSION |