Permit: T08CM00366

Parcel: 12215215A


Addresses:

3350 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00366

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PARTIAL ROUGH IN WALLS, ROOM #'s 200, 218, 219, 220
04/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER MAIN LEVEL
04/17/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
DO NOT ONE SIDE WITHOUT APPROVAL
1. PROTECT ENT IN WALLS
2. SUPPORT VDV CABLING IN WALLS - 725.24
3. SUPPORT MC CABLE 330.30
4. PROTECT VDV CABLING FROM SHARP METAL EDGES
5. EXTERIOR WALL COVERED WITHOUT INSPECTION -
PLEASE REMOVE
6. HAVE ENGINEER AUTHORIZE USE OF ENT -
PLANS CALL FOR 1" CONDUIT

*NOTE: 725.3 & 24, 800.3 & 24, 300.11 WILL APPLY