Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00366
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PARTIAL ROUGH IN WALLS, ROOM #'s 200, 218, 219, 220 |
|
04/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER MAIN LEVEL |
|
04/17/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT ONE SIDE WITHOUT APPROVAL 1. PROTECT ENT IN WALLS 2. SUPPORT VDV CABLING IN WALLS - 725.24 3. SUPPORT MC CABLE 330.30 4. PROTECT VDV CABLING FROM SHARP METAL EDGES 5. EXTERIOR WALL COVERED WITHOUT INSPECTION - PLEASE REMOVE 6. HAVE ENGINEER AUTHORIZE USE OF ENT - PLANS CALL FOR 1" CONDUIT *NOTE: 725.3 & 24, 800.3 & 24, 300.11 WILL APPLY |