Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00365
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LABEL METER & FUSES |
|
04/21/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL PROTECTIVE BUSHINGS ON CONDUCTORS #4 OR LARGER 2. AIC RATING OF BREAKERS @ PANEL TO BE 42,000 AIC SEE SHEET E-01 |
|
04/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER OF WALLS |
|
03/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR CEILING, WALLS |
|
02/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERSLAB FOR FLOOR BOX |