Permit: T08CM00354

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00354

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORIES (BOTH) TO BE CORRECT, LEGIBLE, BREAKERS TO BE NUMBERED IN PANEL "L"
2. CHECK EMERGENCY LIGHTING
3. TRANSFORMER G.E.C HAS BROKEN STRANDS - REPAIR/REPLACE
4. REMOVE UNUSED WIRING & EQUIPMENT
5. FINISH LOW VOLTAGE WIRING
6. FIRE ALARM WIRING TO BE RED - NOT PAINTED WHITE
7. HAVE REVERSE POLARITY OFFICE RECEPTACLE - CHECK ALL

PARTIAL INSPECTION
GO THROUGH WORK BEFORE YOU CALL IN
MAKE SURE PER CODE & PLAN
PANELS & X-FORMER TO BE OPEN
03/13/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR FINAL WHEN ALL WORK IS DONE & SPACE IS READY TO OCCUPY