Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM00352
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1. PROVIDE A TRAP ON SECONDARY DRAIN. 2. TERMINATE OVER WINDOW. 3. MARK FAN COIL DATA PLATE WITH PROPER HEAT STRIP & FUSE ACCORDINGLY 4. WILL CHECK ON FINAL 5. OK FOR SHEETROCK |
|
11/12/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE THE BATHROOM EXHAUST DUCT IN WALL. 2. USE 4" EXHAUST DUCT AFTER TEE 3. PROVIDE A SHEET METAL TEE FOR EXHAUST DUCTS 4. TAPE IS NOT APPROVED HANGER STRAP 5. PROVIDE R8 DUCT INSULATION IF DUCT IS ABOVE ATTIC INSULATION 6. PROVIDE A TRAP ON CONDENSATE DRAIN 7. USE PRIMER PRIOR TO GLUING PVC FITTINGS 8. PROVIDE A SECONDARY DRAIN 9. FINISH INSULATING REFER LINES 10. MECHANICALLY FASTEN ALL EXHAUST DUCTS TO FANS & TEES 11. PROVIDE LISTING FOR DUCT BOARD R VALUE |