Permit: T08CM00352

Parcel: 13101002F


Addresses:

4880 E 29TH ST 14


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM00352

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1. PROVIDE A TRAP ON SECONDARY DRAIN.
2. TERMINATE OVER WINDOW.
3. MARK FAN COIL DATA PLATE WITH PROPER
HEAT STRIP & FUSE ACCORDINGLY
4. WILL CHECK ON FINAL
5. OK FOR SHEETROCK
11/12/2008 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE THE BATHROOM EXHAUST DUCT IN WALL.
2. USE 4" EXHAUST DUCT AFTER TEE
3. PROVIDE A SHEET METAL TEE FOR EXHAUST DUCTS
4. TAPE IS NOT APPROVED HANGER STRAP
5. PROVIDE R8 DUCT INSULATION IF DUCT IS ABOVE ATTIC INSULATION
6. PROVIDE A TRAP ON CONDENSATE DRAIN
7. USE PRIMER PRIOR TO GLUING PVC FITTINGS
8. PROVIDE A SECONDARY DRAIN
9. FINISH INSULATING REFER LINES
10. MECHANICALLY FASTEN ALL EXHAUST DUCTS TO
FANS & TEES
11. PROVIDE LISTING FOR DUCT BOARD R VALUE