Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED COPY OF FIELD EVALUATION |
|
| 03/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ALL NEW IMAGING EQUIPMENT & ASSOCIATED SUPPORT EQUIPMENT TO BE LISTED - PLEASE VERIFY LISTING OF EQUIPMENT |
|
| 02/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL PANEL DIRECTORIES 2. NEED PLAQUE @ SES STATING LOCATION OF BACK UP POWER LOCATIONS AND TYPES 3. PROVIDE TEST REPORT FOR NEW GEN. SET 4. INSTALL BONDING BUSHINGS OR RACEWAYS THROUGH CONCENTRICS WHEN 480V/277V 5. WHEN IS MEDICAL EQUIPMENT TO BE INSTALLED |