Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/22/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 05/19/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/15/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. BROKEN WALLS TO INSPECT ADDED WORK 2. SUPPORT WIRES TO BE AS PER 300.11 #3 & #1 PREVIOUS INSPECTION |
|
| 05/14/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT VDV CABLING PER 725.24, 800.24, 300.11 2. ATTACH FIXTURES TO GRID 410.6 3. SUPPORT M/C CABLE PER 300.11 4. SCREW TO BE 2 ON CENTERS OR 4 ON CORNERS 5. MOVE EXIT LIGHT BELOW GRID AND AS PER 700.12 6. BOX OVERFILLED *MORE ELECTRIC HAS BEEN ADDED TO WALLS - ADD TO PLANS AND CALL FOR INSPECTION |
|
| 05/13/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |