Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM00342

Parcel: 12101103K

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/28/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/22/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
05/19/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/15/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. BROKEN WALLS TO INSPECT ADDED WORK
2. SUPPORT WIRES TO BE AS PER 300.11
#3 & #1 PREVIOUS INSPECTION
05/14/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT VDV CABLING PER 725.24, 800.24, 300.11
2. ATTACH FIXTURES TO GRID 410.6
3. SUPPORT M/C CABLE PER 300.11
4. SCREW TO BE 2 ON CENTERS OR 4 ON CORNERS
5. MOVE EXIT LIGHT BELOW GRID AND AS PER 700.12
6. BOX OVERFILLED

*MORE ELECTRIC HAS BEEN ADDED TO WALLS - ADD TO PLANS AND CALL FOR INSPECTION
05/13/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*