Permit: T08CM00342

Parcel: 12101103K

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/28/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/22/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4" 314.20
2) USE APPROVED HARDWARE TO MOUNT DEVICES
3) PLEASE PROVIDE MFG INSTRUCTIONS FOR FLOOR BOX COVER AND SEPERATION
4) PANEL DIRECTORY TO BE PER 408.4-NO ABREVIATIONS
5) EM/EXIT LIGHTS TO BE PER 700.12
6) EXIT LIGHT NOT WORKING
7) REVISE PLANS FOR LIGHTING CHANGES AND ADDED ELECTRIC
8) IDENTIFY GROUND CONDUCTOR
9) CANNOT USE SHEET METAL SCREWS TO HOLD GROUND BAR
10) LABEL PANEL COVERS ON OUTSIDE OF COVER
11) PROVIDE LOCK ON DEVICE PER PLANS
05/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK WALL RECEPTION RELOCATED SWITCH
- OK CEILING TILES AFTER SUPPORT WIRES CONNECTED
AT BOTH ENDS
04/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER
04/24/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS