Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/22/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" 314.20 2) USE APPROVED HARDWARE TO MOUNT DEVICES 3) PLEASE PROVIDE MFG INSTRUCTIONS FOR FLOOR BOX COVER AND SEPERATION 4) PANEL DIRECTORY TO BE PER 408.4-NO ABREVIATIONS 5) EM/EXIT LIGHTS TO BE PER 700.12 6) EXIT LIGHT NOT WORKING 7) REVISE PLANS FOR LIGHTING CHANGES AND ADDED ELECTRIC 8) IDENTIFY GROUND CONDUCTOR 9) CANNOT USE SHEET METAL SCREWS TO HOLD GROUND BAR 10) LABEL PANEL COVERS ON OUTSIDE OF COVER 11) PROVIDE LOCK ON DEVICE PER PLANS |
|
| 05/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK WALL RECEPTION RELOCATED SWITCH - OK CEILING TILES AFTER SUPPORT WIRES CONNECTED AT BOTH ENDS |
|
| 04/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER |
|
| 04/24/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |