Permit: T08CM00340

Parcel: 109250170

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/15/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NON-METALLIC TUBING NOT LISTED

OK WALLS AFTER CORRECTIONS

RECEIVED LETTER FOR M/C CABLE
02/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT M/C AT STUDS
2. SUPPORT M/C PER 330.30
3. REMOVE INSULATION TO GROUND SCREWS
4. PLANS CALL FOR CONDUIT
5. INSTALL DATA AS PER PLANS TO INSPECT
6. ON VERTICALS USE APPROVED STRAPS

*VDV CABLING TO BE AS PER 725.6, 800.24, 300.11