Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NON-METALLIC TUBING NOT LISTED OK WALLS AFTER CORRECTIONS RECEIVED LETTER FOR M/C CABLE |
|
| 02/29/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT M/C AT STUDS 2. SUPPORT M/C PER 330.30 3. REMOVE INSULATION TO GROUND SCREWS 4. PLANS CALL FOR CONDUIT 5. INSTALL DATA AS PER PLANS TO INSPECT 6. ON VERTICALS USE APPROVED STRAPS *VDV CABLING TO BE AS PER 725.6, 800.24, 300.11 |